UT-512 Insulation resistance meter 2500 V 100 GOhm

Description

LCD display:
- main digital: values from 0 to 10000
- secondary digital: for displaying measurement voltage
- analogue scale: 30 segments
Automatic measurement range selection
Output voltage: 500 V/ 1000 V/ 1500 V/2500 V; error 0 ~ 20%
Insulation resistance:
- 500 V - 0.5 MOhm … 5 GOhm; error ±3% ±5 counts
- 1000 V - 2 MOhm … 10 GOhm; error ±3% ±5 counts
- 1500 V - 5 MOhm … 20 GOhm; error ±3% ±5 counts
- 2500 V - 10 MOhm … 100 GOhm; error ±3% ±5 counts
Short-circuit current: < 1.8 mA
DC voltage measuring range: 30 V … 600 V; error ±2% ±5 counts
AC voltage measuring range: 30 V …600 V (50/60 Hz); error ±2% ±5 counts
Data memory: 18 values
USB interface for PC communication
Polarisation index measurement
Measurement timer: up to 15 minutes
Low battery indicator
Comparative measurements
Display backlight
Automatic discharge
Operating temperature range: 0°C ... 40°C
Storage temperature range: -20°C ... 60°C
Relative humidity: not more than 85%
Power supply: batteries 8 pcs. x 1.5 V type LR14, mains adapter
Kit contents: instrument, battery set, test leads (red, green, black), accessory case, mains adapter

Registered in the Uzstandart register
Warranty for manufacturing defects, including measurement accuracy and successful passing of Uzstandart metrological verification: 12 months


Weight, kg4